Air changes per hour (ACH) is how many times a room’s full volume of air is replaced in an hour. In sterile processing the answer depends on the room: dirty instruments get the most protective air handling, and clean areas get less, but the air always pushes outward from the cleanest space. Under the ASHRAE 170/FGI tables that most facilities are built and inspected to, decontamination needs at least 6 air changes per hour at negative pressure. Prep and pack and sterile storage need at least 4 at positive pressure, with at least 2 of each from outdoor air. AAMI and a joint industry recommendation call for 10 per hour in decontamination, prep and pack, and one-room processing.
Air Change Requirements Room by Room
- Decontamination room: negative pressure, at least 2 outdoor and 6 total air changes per hour, all air exhausted outdoors, no in-room recirculating units, 60–73°F (16–23°C).1FGI Guidelines. Sterile Processing Department Design and HVAC Considerations
- Clean workroom (prep and pack): positive pressure, at least 2 outdoor and 4 total air changes per hour, humidity no higher than 60%, 68–73°F (20–23°C).1FGI Guidelines. Sterile Processing Department Design and HVAC Considerations
- Sterile storage: positive pressure, at least 2 outdoor and 4 total air changes per hour, humidity no higher than 60%, no warmer than 75°F (24°C).1FGI Guidelines. Sterile Processing Department Design and HVAC Considerations
- One-room setup: a one-room sterile processing setup is recommended to have 10 air changes per hour, humidity no higher than 60%, and 60–73°F.1FGI Guidelines. Sterile Processing Department Design and HVAC Considerations
The total air change number already includes the outdoor air number, so the two are not added together. All of these values are minimums, and exceeding them is allowed.
Pressure direction is part of the requirement. Negative pressure means air flows into the room from the hallway, so contamination stays inside decontamination.2ESP LLC. Designing Airflow Pressures In CSSD Positive pressure means air flows out of the room, keeping dust and microbes away from clean and sterile items.2ESP LLC. Designing Airflow Pressures In CSSD Some international documents also call for decontamination to sit at least 2.5 pascals below neighboring rooms, with no recirculated air.3PubMed Central. Negative pressure of the environmental air in the cleaning area of the materials and sterilization center: a systematic review ASHRAE 170 points readers to AAMI ST79 for more detail on these spaces.4ASHRAE Standard 170-2017. Ventilation of Health Care Facilities
At the doorway, the check is directional. Air should move from the corridor or clean side toward decontamination, and a gauge or a smoke test at the door gap shows which way it is going. Decontamination usually has a separate entrance for soiled items and a path out to the clean side, so the room has to hold its pressure direction while carts and staff pass through.
The outdoor number deserves its own look. Outdoor air is fresh air brought in from outside, and it counts toward the total. A decontamination room at 6 total can therefore be 2 outdoor and 4 recirculated through the central system, as long as none of it is recirculated within the room. When you check drawings or test reports, look for both numbers in each room’s entry, because a report that gives only total air changes doesn’t show whether the outdoor minimum is met.
Sterile storage numbers agree across standards. The ASHRAE 170 table cited by The Joint Commission lists the same values: positive pressure, 4 total and 2 outdoor changes, humidity no higher than 60%.5The Joint Commission. Do we need to monitor the temperature and humidity of the rooms where sterile supplies are stored? AORN’s sterile storage guidance matches, with at least 4 air changes, positive pressure, humidity no higher than 60%, and no warmer than 78°F.6Air Innovations. A Sterile Storage Standards Guide: AORN, AAMI, ASHRAE | Optimal Temperature & Humidity
The 10 for one-room setups is a different case. That space does decontamination, prep, and packing together, so it can’t rely on the separation between rooms that the individual room values assume.
Surveyors usually check against the code edition your state adopted. The higher AAMI targets are best practice unless your facility has committed to them in policy. Document which standard each room was designed to meet.
Why Some Standards Say 10 Air Changes
AAMI recommends 10 in decontamination, against the code minimum of 6.7CDC / PubMed Central. Guideline for Disinfection and Sterilization in Healthcare Facilities Infection control guidance repeats the 10, with at least 2 of them from outside air.8Infection Control Today. IC in Care Series: Sterile Processing
7CDC / PubMed Central. Guideline for Disinfection and Sterilization in Healthcare FacilitiesPrep and pack follows the same pattern. Industry guidance citing AAMI and FGI gives it a minimum of 10 air changes per hour, at least 2 from outside, at positive pressure.9pure-processing.com. Ultimate Guide to Sterile Processing Prep & Pack The FGI table itself lists 4 for the clean workroom, so the 10 reflects the AAMI-aligned recommendation.1FGI Guidelines. Sterile Processing Department Design and HVAC Considerations A separate sterilizer equipment room is also recommended at 10 changes with positive pressure.7CDC / PubMed Central. Guideline for Disinfection and Sterilization in Healthcare Facilities The older CDC table listed the sterilizing room at 10 total changes, exhausted outdoors.10CDC / US Government. Appendix B. Air – Guidelines for Environmental Infection Control in Health-Care Facilities (2003)
The difference comes from who writes each number. AAMI is a standards organization for medical device processing, and its recommended practices guide how departments run but do not carry the force of building code. The FGI guidelines feed the codes that states adopt, which is why the 6 and 4 appear in design and inspection while the 10 appears in recommendations. A department can follow the 10 voluntarily, and some do because they adopt AAMI in their own policies.
The higher target makes sense in these two rooms. Decontamination produces aerosols from brushing, spraying, and rinsing contaminated instruments, so faster dilution lowers what staff breathe in. Prep and pack is where clean instruments are handled and wrapped, so cleaner air reduces what settles on items before sterilization and packaging.
Choosing between the minimum and 10 involves trade-offs. Higher rates increase fan energy and the load on heating and cooling, and older buildings may not physically reach 10 without duct changes.
What Higher Air Changes Actually Do
The CDC calculates the time to remove a contaminant from the air changes per hour and the removal level wanted.11Centers for Disease Control and Prevention. Appendix B. Air The CDC’s well-mixed room table shows about 46 minutes to remove 99% at 6 changes per hour, and about 28 minutes at 10.
Going from 6 to 10 saves about 18 minutes at the 99% level. The table assumes air mixes evenly throughout the room, which real rooms only approximate, so treat its minutes as a best case.
Chemicals add another reason for enough airflow. In one reprocessing room using a peracetic acid sterilant, the airflow was too weak to control odors or keep temperature and humidity in range.12Centers for Disease Control and Prevention. Evaluation of Worker Exposures to Peracetic Acid-Based Sterilant during Endoscope Reprocessing Several signs point to an under-ventilated room: a chemical smell that lingers after reprocessing, fogging or condensation in decontamination, staff complaining of eye or throat irritation, and temperature or humidity readings drifting out of range.
More air isn’t a cure-all. Higher rates only dilute what is in the air; they don’t remove contamination on surfaces, so cleaning routines still matter. Direction of flow matters as much as volume, because exhaust placed away from the work area can pull contaminants across staff first. A room at the code minimum with good airflow and exhaust placement can protect people better than a higher-rate room with poor layout.
How Doors and Traffic Undo Pressure
Frequent door opening disturbs the airflow and can cause containment to fail.13PubMed. Airborne particle dispersion to an operating room environment during sliding and hinged door opening Opening a door can remove the pressure difference between rooms, and can even reverse it.14Building Research & Information. Particle dispersion in a cleanroom – effects of pressurization, door opening and traffic flow In one test room, door openings pushed out air equal to up to 2 air changes per hour, about 10% of the supply air.15PubMed Central. The effect of door opening on air-mixing in a positively pressurized room: Implications for operating room air management during the COVID outbreak Rooms kept at a larger pressure difference regained pressure much faster after a door closed.14Building Research & Information. Particle dispersion in a cleanroom – effects of pressurization, door opening and traffic flow After the door closes, the ventilation system has to rebuild the difference, and that takes time if the difference is small. No setting makes up for propped-open doors, which keep the difference at zero.
This explains why a room can pass inspection but fail in use. Balancing is tested with doors shut, while real shifts involve constant opening and closing. Periodic spot checks during work show the true condition.
A few habits help. Keep pass-through windows and doors closed when not in use. Route soiled carts so they don’t pass through clean areas. Check pressure monitors after heavy traffic periods.
Filter Requirements for Sterile Processing Air
Sterile and clean processing areas need at least two filter stages.16Tex-Air Filters. How Many Air Exchanges Are in Sterile Processing? MERV is the filter rating printed on the filter frame, and higher numbers catch smaller particles. The first filter is rated MERV 8, catching about 30% of fine particles, and the second is MERV 14, about 90%.16Tex-Air Filters. How Many Air Exchanges Are in Sterile Processing?
The coarse MERV 8 stage goes first to keep the fine filter from clogging quickly with large particles. A single filter of either rating does not meet the requirement.
HEPA filters catch at least 99.97% of particles 0.3 micrometers in size and are standard in manufacturing cleanrooms.17Air Filters for Clean Air. How Facilities Managers Can Ensure Cleanroom Air Quality in Sterile Manufacturing HEPA captures a great deal but resists airflow more, so it needs stronger fans and tighter housings. A department that adds HEPA voluntarily is going beyond the requirement, and should check that its air handler can still deliver the design airflow.
Filters and air changes also interact. A clogged filter cuts airflow and lowers the actual air changes per hour. Changing filters on schedule keeps the design rate, and pressure gauges across filters signal when they need replacing.
Checking and Keeping Your Department Compliant
Sterile storage has specific limits for humidity, temperature and pressure, so rooms storing sterile supplies need monitoring.5The Joint Commission. Do we need to monitor the temperature and humidity of the rooms where sterile supplies are stored? The older CDC table set sterile storage humidity at 30–60%.10CDC / US Government. Appendix B. Air – Guidelines for Environmental Infection Control in Health-Care Facilities (2003)
A simple routine covers most of it. Log temperature and humidity at the same time daily in each room, so any drift shows up in the record. Ask facilities to confirm pressure direction on a set schedule using a gauge or a smoke test at the door gap, and write down the result. Keep the logs where you can pull them quickly during a survey, along with notes on any out-of-range reading and what was done.
Air balancing measures actual airflow in each room, so it is the way to confirm air changes per hour rather than assume them. Ask for it after renovation, duct work, fan changes, or filter-system changes, since each can shift airflow. Keep the report, which shows each room’s measured values against the target.
Older departments need extra thought. Their rooms were often built to earlier, lower targets, and upgrades may need larger ducts or extra exhaust. Engineers can measure current flow before you plan changes. Plan the work around keeping decontamination at negative pressure.

